Torkel 900 – Series
Battery Load Unit
The TORKEL™ 900 series is used to perform load/discharge testing which is the only way to determine battery systems actual capacity. Together with the optional cell voltage logger, BVM, connected directly to the TORKEL 900, it becomes a complete, stand-alone, discharge test system.TORKEL comes in three models, 910, 930 and 950, see table below.The high discharge capacity of TORKEL gives the opportunity to shorten the test time. Discharging can take place at up to 220 A, and if higher current is needed, two or more TORKEL units or extra load units, TXL, can be linked together. Tests can be conducted at constant current, constant power, constant resistance or in accordance with a pre-selected load profile. Testing can also be carried out without disconnecting the battery from the equipment it serves. Via a DC clamp-on probe, TORKEL measures the total battery current while regulating it at a constant level. Battery systems can be plus or minus grounded or free floating.The test results can be presented and edited on a PC using the included PC software “TORKEL Viewer.
Gain a comprehensive insight into battery capacity with discharge testing
- Discharge testing for full insight into battery capacity
- Enhanced safety features including spark free connection and emergency safety fuse
- Ability to test the battery without disconnecting it from the system
- High discharge capacity shortens the test time
- A complete stand-alone discharge test system
The TORKEL 900 is the fourth generation in the series of Megger’s trusted battery discharge test systems. Discharge testing is the only test method that provides a comprehensive insight into battery capacity, and is therefore an essential part of vigorous battery maintenance programmes.
Tests can be conducted at constant current, constant power, constant resistance or in accordance with a pre-selected load profile. Together with the cell voltage logger, BVM, now connected directly to the TORKEL 900, it becomes a complete stand-alone discharge test system.
The TORKEL is connected to the battery, the discharge current and the alarm levels (voltage, capacity, time) are set. After starting the discharge TORKEL keeps the current constant at the preset level. When the voltage drops to a level slightly above the final voltage, TORKEL issues an alarm. If the voltage drops so low that there is a risk for deep discharging the battery, TORKEL shuts down the test. All values are stored in TORKEL and can easily be transferred via an USB-stick to a PC for evaluation.
Testing can be carried out without disconnecting the battery from the equipment it serves. Via a DC clamp-on ammeter, TORKEL measures total battery current while regulating it at a constant level. Furthermore, the high discharge capacity of TORKEL gives the opportunity to shorten the test time. Discharging can take place at up to 220 A, and if higher current is needed, two or more TORKEL units or extra load units, TXL, can be linked together.
Key Features
Batteries can be tested in service
Dynamic discharge technology – full power at all voltages
Safety in all details, e.g. detection of blocked airflow
Real time monitoring during test
Easy report function and calibration
Easily expandable for larger battery banks using TXL extra load units
BVM cell monitor control integrated in the system
Other Products
QUASAR
Three Phase Industrial Grade Protective Relay Test Set with cloud technology
Powerful and flexible
- 4 x 300V + 3 x 60A outputs, switchable to 7 current outputs
- 6 binary inputs + 4 binary outputs
- External DC current and voltage measurement
- 6 low-level outputs to test sensors, meters etc, and to upgrade with more channels
- Integral Wi-Fi, Ethernet LAN, dedicated IEC-61850 port and Expansion port
- Field serviceable
Rugged and portable
- 19.5 kg (43 lb)
- Integral ABS casing with wheels and extensible handle. No separate travel case needed.
Familiar User Interface
- Conduct quick or pre-configured tests directly from your tablet or smartphone
- Connect to your Windows computer for automated, exhaustive testing
VLF SIN 62
VLF sine wave test system for medium voltage cables with integrated Tan Delta
- Performs cable withstand testing, cable diagnosis, and sheath fault pinpointing
- Smallest and lightest unit on the market in its class
- Unique user-experience, thanks to a large, colour touch screen
- Automatic result interpretation as per latest IEEE 400.2 standard
- High safety, thanks to its analogue residual voltage indicator
TDM 45
High power test and diagnosis combination for MV cables (Tan Delta, VLF and PD)
- Cable testing, cable diagnosis, and sheath testing in one device
- Enables standard compliant high power VLF testing at 0.1 Hz (5 µF at 40 kV RMS)
- Internal tan delta measurement with automatic result interpretation
- Partial discharge diagnosis using VLF sine wave, damped AC or 50/60 Hz slope technology voltages