VentPro Batteries
Nickel Cadmium Regulated Pocket Plate Batteries
HBL with its global experience in Ni-Cd batteries has pioneered the development of next generation Nickel Cadmium Valve Regulated Pocket Plate Batteries – VentProThis Ultra-low maintenance version provided with upgraded performance parameters replaces VRPP – “first generation” Ni-Cd Valve Regulated Pocket Plate batteriesVentPro range is designed to comply with IEC 62259 and certified by Intertek VentPro ranges offer a recombination gas efficiency of more than 95%. No water additions are required in normal useAvailable in a choice of plate types – designed to specific application requirementsVentPro range is offered in medium discharge HVM and long discharge HVL types
Medium Discharge – HVM:
- For medium/short discharge applications, up to 3 hours backup time requirements
- 7 Ah to 1340 Ah
- 63 standard cell models to choose from
Long Discharge – HVL:
- For long discharge applications, with more than 3 hours backup time requirements
- 15 Ah to 1680 Ah
- 66 standard cell models to choose from
Superior Features & Benefits
- Ultra-low maintenance version – No water additions required when operated under recommended conditions
- Excellent charge acceptance – More than 90% capacity available when charged at 1.42V for 15 hours @ 0.1C5 A
- Improved discharge performance
- Exceptional gas recombination efficiency (>95%), better than IEC specified requirements.
- Long battery life – 20years+ at 20 deg C for standby float applications
- Better performance even at low temperatures (<20 deg C)
- Wide range of capacities, eliminates need for parallel strings
- Almost double the number of intermediate models as compared to leading competitors, resulting in the most optimal battery selection
- Best TCO (Total Cost of Ownership) for demanding application needs
- Available in two cell types – Medium Discharge (HVM) & Long Discharge (HVL)
- Built on rugged Ni-Cd Pocket Plate technology, no risk of sudden death failure
Product Range
- For medium/short discharge applications, up to 3 hours backup time requirements
- 7 Ah to 1340 Ah
- 63 standard cell models to choose from
- For long discharge applications, with more than 3 hours backup time requirements
- 15 Ah to 1680 Ah
- 66 standard cell models to choose from
Applications
-
- Oil and gas
- Utilities
- Switching substations
- Emergency lighting
- UPS
- Fire alarm systems
- Signaling
Key Features
Terminal Arrangement
Nickel-plated components (tab, stud, nut, post) provide excellent electrical conductivity
Plate Groups
Bolted construction under controlled torque conditions to withstand severe vibrations
Special Polypropylene Fibrous Separator
(Facilitates recombination)
Self-resealing Low Pressure Vent Cap
(Releases any excess gases inside the cell)
Splash Guard
Prevents electrolyte splashing and possible short-circuit caused by external objects accidentally falling into the cell
Pocket Plate
Made of double perforated steel strips, encapsulating the active materials
Translucent Polypropylene Container
Fusion welded to lids, makes the cell mechanically sturdy and facilitates visual inspection of electrolyte level
Other Products
TOR-1
Transformer Oil Express Test Kit TOR detects moisture in oil quickly and precisely – even in miniscule quantities.
Express test kits have been developed specifically to detect the amount of moisture in dielectric insulation oils, which is necessary for normal operation and timely maintenance of electric equipment. The high precision and excellent long-term stability make this testing device an ideal solution for continuous monitoring of moisture in transformer oils.
The test kit is compact, reliable, simple to operate and multifunctional; it is the best choice for moisture measurement. The device also measures such parameters as water activity (aw), temperature (t), and calculates absolute water content in ppm. The device combines everything necessary for simple and comfortable operation: two digital displays to indicate sample temperature moisture content in ppm, a detachable sample container and two buttons: power and measurement.
TOR-80
The TOR-80 unit is designed to determine the electric breakdown voltage of transformer oil and other liquid dielectrics in accordance with IEC 60156, ASTM D877, ASTM
D1816, GOST 6581. It is a fully automatic device that allows testing to be performed according to the procedures specifed in these standards, as well as user procedures specifed in the
appropriate section of the setup menu.
GUIDE PS400
The Guide PS Series high-performance thermal camera is designed to make the inspection, maintenance and troubleshooting work easier, faster and more accurate.